pid-temperature-controller.png
Product Description :
Standard: P10
Process Control: P11
Dim.: 48x48mm
 
Product Features :
  • 16bit microprocessor operating core doing PID + Self-tuning.
  • Various options of input signals (thermocouples, RTD, analog signals, etc.).
  • Main control output can select relay, pulse voltage, linear analog signals.
  • Can drive all types of contactors, SSR, SCR, 3-line proportional motor valve, etc.
  • Can set reverse / forward control (heating or cooling process).
  • Dual-output models can do cooling / heating two-way PID controlling.
  • Set Value (SV) can employ analog signal input to achieve Remote Set Value setting (RSV).
  • 26 types of alarm modes for option; can be added with broken-line detecting alarm function (HBA).
  • Re-transmission function can convert Present Value (PV) or controlling output amount into analog signal output for recorder or other applications.
  • Provided with manual output mode.
  • Serial communication function supports RTU and ASCII format of Modbus. The Baud rate can reach as fast as 38,400 bit/s.
  • Programmed controlling provides 16 temperature levels whose operating intervals and repeat frequency can be planned freely.
 
Model Explanation :
Item Explanation
P10 - 1
0
1 0 - 0 0 0
A
1   2 3 4 5   6 7 8 9
1 Model P10 48*48mm
P11 Procedure Control
2 Output 1 0 none 1 Relay 2 Logic voltage (SSR) 3 4~20mA
4 0~5V 5 1~5V 6 0~10V 7 2~10V
8
3 lines proportional valve control
3 Output 2 0 none 1 Relay 2 Logic voltage (SSR) 3 4~20mA
4 0~5V 5 1~5V 6 0~10V 7 2~10V
4 Alarm 0 none 1
1
2 2 3 2
A HBA(50A) B
HBA+AL2
C
HBA+AL2,3
D HBA(100A) E
HBA+AL2
F
HBA+AL2,3
5 Input Type 0
Thermocouple
1
RTD
3
4~20mA
4
0~5V
5
1~5V
6
0~10V
7
2~10V
6 Remote SV 0
none
3
4~20Ma
4
0~5V
5
1~5V
6
0~10V
7
2~10V
7 Transmitting output 0
none
3
4~20mA
4
0~5V
5
1~5V
6
0~10V
7
2~10V
8 Comm. 0
none
1
RS232
2
RS485
 
Product Specifications :

 

Model P10 P20 P30 P50 P60
Size 48x48mm 48x96mm 96x48mm 72x72mm 96x96mm
Power Supply AC 90 ~ 240V (60/50Hz); DC 24V (optional)
Power
Consumption
4VA 4VA 4VA 5VA 5VA
Unit Weight 130g 200g 200g 200g 280g
Storage / Operating Temperature 0 ~ 65°C / 0 ~ 50°C; 20 ~ 90% RH
Data Backup
Memory
EEPROM, 10 years
Accuracy
0.2% FS ± 1DIG
(except for thermocouples of B and S type)
Digit Height (mm)
PV (red)
SV (green)
 
10
 
11
 
14
 
14
 
14
10 11 10 11 11
Alarm Output Relay contact 8A, 250VAC
Controlling Measure On/Off, P, PI, PD, PID controlling
Controlling
Output
Relay
A contact
5A / 250V
A, B contacts
8A / 250V
Logic Voltage PWM pulse voltage (to drive SSR): On=24V, Off=0V (20mA Max.)
Linear Analog
Current: 0 ~20mA, 4~20mA (Input Impedance: 600Ω Max.)
Voltage: 0~5V, 1~5V, 0~10V, 2~10V (Input Impedance: 1KΩ Max.)
Input Type
Thermo-
couple
K, J, R, S, B, E, N, T, W3, W5, PL-II
(Input Impedance: approx. 1KΩ Max.)
RTD PT-100 (DIN), JPT-100 (JIS)
Linear Analog 0~10mV, 0~20mV, 0~50mV, 4~20mA, 0~10V…