inductive-sensor-nj4-12gk-n-p-f-viet-nam-anh-nghi-son.png
General specifications
Switching function Normally closed (NC)
Output type NAMUR
Rated operating distance 4 mm
Installation non-flush
Assured operating distance 0 ... 3.24 mm
Reduction factor rAl 0.4
Reduction factor rCu 0.3
Reduction factor r304 0.85
Nominal ratings
Nominal voltage 8.2 V (Ri approx. 1 kΩ)
Switching frequency 0 ... 1500 Hz
Current consumption  
  Measuring plate not detected min. 3 mA
  Measuring plate detected ≤ 1 mA
Functional safety related parameters
MTTFd 11774 a
Mission Time (TM) 20 a
Diagnostic Coverage (DC) 0 %
Compliance with standards and directives
Standard conformity  
  NAMUR EN 60947-5-6:2000 
IEC 60947-5-6:1999
Approvals and certificates
FM approval  
  Control drawing 116-0165
UL approval cULus Listed, General Purpose
CSA approval cCSAus Listed, General Purpose
CCC approval CCC approval / marking not required for products rated ≤36 V
Ambient conditions
Ambient temperature -25 ... 100 °C (-13 ... 212 °F)
Mechanical specifications
Connection type cable PVC , 2 m
Core cross-section 0.34 mm2
Housing material PBT
Sensing face PBT
Housing diameter 12 mm
Degree of protection IP66 / IP68
Cable  
  Bending radius > 10 x cable diameter
General information
Use in the hazardous area see instruction manuals
  Category 2G; 1D